Royal Delkor DC31 100 A/H Marine Deep Cycle Battery 12 Volts 100 A/H...
POWEROAD 6 Volt 4AH Sealed Lead Acid AGM Battery Please contact us for...
CSB HR1234WF2 Sealed Lead Acid Battery 5 Year Design Life 12 Volts 9...
Mecer IVR-2400LBKS Series 2400VA Plug and Play Inverter/Charger with...
CSB GP1272F2 Sealed Lead Acid Battery 5 Year Design Life 12 Volts 7.2...
CSB HRL634WF2 Sealed Lead Acid Battery 8-10 Year Design Life 6 Volts 9...
Leisure Battery box with lockable lid for 12V 100Ah Battery Versatile,...
CEIL DSP Based 1450 VA - 1170 Watt Plug and Play Pure Sine Wave...
Royal Delkor 1150K 102 A/H Storage Battery 12 Volts 102 A/H Sealed...
CEIL 1450VA / 1160W Pure Sine Wave Inverter / Charger Steel Battery...
CEIL 1450VA / 1160W Pure Sine Wave...
ME-2000-WPTU
New product
Mecer 2kVA Plug and Play On-line Single Phase Input and Output UPS
Email: info@createenergy.co.za or telephone: +(27) 11 888 0410
2-4 Days Availability (Ex Stock, Midrand Supplier Warehouse)
Warning: Last items in stock!
Availability date:
*Product Specifications are subject to change without prior notice.
This Online UPS is a high frequency unit specifically designed for servers, data-center critical network devices, sensitive electronic equipment, telecom, banks, hospitals etc.
The output load is always fed from the UPS inverter and the batteries being charged via AC utility power.
When the utility power shuts down, the output power is fed from the internal battery to keep a stable output power supply.
Emergency power off function only available for 6K and up models
SKU | ME-2000-WPTU |
---|---|
WEIGHT | 17.000 |
PHYSICAL DIMENSIONS | 397 x 145 x 220 (mm) |
CAPACITY | 2000 VA / 1600 W |
VOLTAGE RANGE LOW LINE TRANSFER | 160VAC/140VAC/120VAC/110VAC±5% ( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0) |
VOLTAGE RANGE LOW LINE COMEBACK | 168VAC/148VAC/128VAC/118VAC ± 5 % ( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0) |
VOLTAGE RANGE HIGH LINE TRANSFER | 300 VAC ± 5 % |
VOLTAGE RANGE HIGH LINE COMEBACK | 290 VAC ± 5 % |
FREQUENCY RANGE | 40Hz ~ 70 Hz |
PHASE | Single phase with ground |
POWER FACTOR | ≧ 0.99 @ nominal voltage (input voltage) |
OUTPUT VOLTAGE | 200/208/220/230/240VAC |
AC VOLTAGE REGULATION (BATT. MODE) | ±1% (Batt. Mode) |
FREQUENCY RANGE (SYNCHRONIZED RANGE) | 47 ~ 53 Hz or 57 ~ 63 Hz |
FREQUENCY RANGE (BATT. MODE) | 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz |
OVERLOAD | Sounding twice every second |
CURRENT CREST RATIO | 3:1 |
HARMONIC DISTORTION | ≦ 3 % THD (linear load) ≦ 6 % THD (non-linear load) |
WAVEFORM (BATT. MODE) | Pure Sinewave |
AC TO DC | Zero |
INVERTER TO BYPASS | 4 ms (Typical) |
AC MODE | 89% |
BATTERY MODE | 87% |
BATTERY TYPE | 12 V / 9 AH |
NUMBERS | 4 |
RECHARGE TIME | 4 hours recover to 90% capacity (Typical) |
CHARGING CURRENT | 1.0 A (max.) |
CHARGING VOLTAGE | 54.7 VDC ± 1% |
BATTERY TYPE & NUMBERS | No |
CHARGING CURRENT | No |
CHARGING VOLTAGE | No |
HUMIDITY | 20-90 % RH @ 0- 40°C (non-condensing) |
NOISE LEVEL | Less than 50dBA @ 1 Meter |
OPTIONAL USB/RS-232 PORT | Supports Windows® 2000/2003/XP/Vista/2008/7, Linux, Unix and MAC |
OPTIONAL SNMP | Power management from SNMP manager and web browser |
Model | Number of Batteries | Encasement | 100% Load Backup Time | 75% Load Backup Time | 50% Load Backup Time | 25% Load Backup Time |
ME-2000-WPTU | 4 | Internal | 4 Minutes | 6.5 Minutes | 12 Minutes | 26 Minutes |